Type the greenhouse’s size and site. The calculator starts from the standard 8 cubic feet a minute per square foot of floor, adjusts for elevation, light and how much warming you accept, and counts the fans.
The worked example is a made-up 24 by 48 ft school greenhouse at 1,000 ft. Nothing you type leaves this browser.
Loading the calculator. If nothing appears, turn on JavaScript.
Measure the floor inside the walls. Average height is the sidewall height plus half the rise to the ridge.
Enrichment · Cultural StudiesFree
Floor area, three factors, then fans.
On a summer day the sun pours roughly the same heat onto each square foot of a greenhouse floor, whatever the roof height. The standard design rate removes it with 8 cubic feet of air a minute per square foot, which holds the rise from inlet to fan to about 7 °F at sea level under 5,000 footcandles.
At higher elevation air is thinner and carries less heat per cubic foot, so you need about 4 percent more air per 1,000 ft. Brighter light means more heat; a smaller allowed temperature rise means more air. Shade cloth or whitewash lowers the light factor, which is often cheaper than another fan.
The worked example is made up. Check the fan maker’s data at your static pressure before buying. Your entries stay in this browser. Support: team@caveatacademic.com.